Széleskörűen alkalmazható hőmérséklet szabályzás területén.
Pl.: fűtés, hűtés, keltetőgépbe, sörfőzéshez, pálinkafőzéshez, légkondicionáláshoz, stb...
Mérete : 50*40*15 mm
Hőmérséklet tartomány : 0-99.9 C fok
Szabályozási pontosság : 0.1 C fok
Érzékelő : NTC (10K / 3435)
Hőmérséklet pontosság : 0.5 C
Érzékelő szonda hossza : kb. 1 méter
Kapcsoló terhelhetősége : AC 10A / 220V
Működési hőmérséklet tartomány : 0 - 50 C
Tápellátás : 12V
How to use:
Connect the power supply and the load, you can supply to the controller,
Is displayed as a measured temperature,
Press the SET button, the display flashes the temperature,
Press - to set the desired temperature,
After setting press SET to confirm return,
The controller automatically performs the relay by setting off!
Lights, LED status descriptions:
Indicator: Off The relay is switched off, Always indicate the relay is closed.
LED: Shows LL is the sensor open, showing ?HH is out of range, the thermostat will be forced to close the relay, the display --- as high temperature protection.
Programming
If you press the “SET” button and hold for more than 5 seconds, the thermostat switches to the settings.
The available settings are:
P0 - selection of the heater or cooler.
P1 - hysteresis (0.1-15 ° C, the default 2 ° C)
P2 - the task of the upper working temperature limit (default 110 ° C)
P3 - the task of the lower working temperature limit (default -50 ° C)
P4 - temperature correction (-7 + 7 ° C, default 0)
P5 - the delay on / off switch (0-10 sec., Default 0)
P6 - over temperature alarm signal (0 +110 ° C, the default is off)
Use the “+” or “-” buttons to select between P0 and P6.
Use the “Set” button to enter a desired field.
If you are intending to use the module for heating applications ensure that P0 = H
Once all the settings have been made. You may use the “+” or “-” buttons to change the set point.
Definitions:
Hysteresis - The temperature difference that is needed between the set point and actual reading, to switch
the relay on again after switching off. Thus meaning if our set point is 65°C and our Hysteresis is 2°C and our
process medium is 50°C the following steps will occur.
1) Relay = ON
2) Temperature rises to 65°C
3) Relay = OFF
4) Process medium cools down to 63°C (2°C lower than Set Point)
5) Relay = ON
6) Return to step 1
Delay - Time taken for the relay to respond to a change in the process